Engineering Materials·MCQ explained

As per IS 2770 (Part 1), the load at failure in a pull out test is 180 kN. Calculate the bond strength if bar diameter = 20 mm and embedded length = 300 mm.

Try it first: pick an option, then read the explanation.

Correct answer: A. 30/π N/mm²

Detailed Explanation: Bond Strength from Pull-Out Test (IS 2770 Part 1)

Why A (30/π N/mm²) is correct: In a pull-out test, the reinforcing bar is pulled axially until it slips or fails. The bond stress is assumed to be uniformly distributed over the lateral surface area of the embedded bar. The formula for average bond strength is derived from this assumption.

Bond Strength Formula

Bond Strength (τ) = P / (Lateral surface area of embedded bar)

Lateral surface area = π × d × L

Given:
P (Load at failure) = 180 kN = 180 × 10³ N
d (bar diameter) = 20 mm
L (embedded length) = 300 mm

Lateral surface area = π × 20 × 300 = 6000π mm²

τ = (180 × 10³) / (6000π)
τ = 180,000 / 6000π
τ = 30 / π N/mm² ≈ 9.55 N/mm²

Understanding the Pull-Out Test (IS 2770 Part 1)

ParameterDescription
PurposeTo determine the average bond strength between steel bar and concrete
Test setupBar embedded in a standard concrete cube; pulled axially using hydraulic jack
Failure modeEither bond failure (bar slips) or tensile failure of bar (bar yields/breaks)
Bond strengthUniform stress assumed over embedded surface area

Why Bond Strength Matters

  • Bond strength ensures composite action between steel and concrete in RCC.
  • Higher concrete grade, deformed bars, and greater cover all increase bond strength.
  • IS 456:2000 specifies minimum development length based on design bond stress.
  • Calculation: τ = P / (πdL) = 180,000 / (6000π) = 30/π ≈ 9.55 N/mm²